• Arm
  • Rus
  • Eng
  • Home
  • About us
  • Products
  • Our News
  • Services
  • Events
  • Contacts
  • Arm
  • Rus
  • Eng
  • Home
  • About us
  • Products
  • Our News
  • Services
  • Events
  • Contacts
  • Home
  • About us
  • Products
    • Heating Heating
    • Air Conditioning Air Conditioning
    • Water supply Water supply
    • Ventilation Ventilation
  • Our News
  • Services
  • Events
  • Contacts
Heating Heating
Air Conditioning Air Conditioning
Water supply Water supply
Ventilation Ventilation
  • Heating
    • DESIGN RADIATORS
    • BOILERS
    • PIPES
    • REMOTE CONTROL
    • PUMP
    • FITINGS
    • GAZ BOILERS
    • TOWEL RAILS
    • EXPANSION AND SURGE TANKS
    • RADIATORS
    • FANCOILS
  • Air Conditioning
    • PIPES
    • REMOTE CONTROL
    • FANCOILS
  • Water supply
    • REMOTE CONTROL
    • EXPANSION AND SURGE TANKS
    • FITINGS
    • PIPES
    • asdasdUS
    • PUMP
  • Ventilation
    • REMOTE CONTROL
    • VENTILATORS

Brands

  • APE
  • DAB
  • FAR
  • FIV
  • IMERA
  • Rhoss
  • TERMINUS
  • INDUSTRIE PASOTTI SpA
  • VARMANN
  • KME
  • Lamborghini
  • Rapido
  • Styleboiler
  • REFLEX
  • UNIDELTA
  • UPONOR
  • Soler & Palau
  • FV-Plast
YARDyEV

Universal YardyEv fan coils are designed to create a comfortable micro-climate in premises of any type. Due to its wide range of performances, presence of body, ability of hiden or duct mounting the maximum flexibility of installation is provided. Fancoils YardyEV provide optimum comfort, including standpoint of the noise level. Due to the aerodynamically optimized construction and lack of vibration, an exceptionally low noise level of fan at any speed is provided. 

Performances 

Housing performances 
MVP - for vertical wall or floor (on special supports) installation, air suction from below, supply of treated air upwards. 
MVT - for vertical floor mounting, front air suction, supply of treated air upwards.
MOP - for horizontal ceiling mounting, air suction from below, supply of treated air ahead.
MOT - for horizontal ceiling mounting, air suction from below, supply of treated air ahead. 
Recessed performances 
IVP - for wall instalation, sucktion air from below, supply of treated air upwards. 
IVF - for wall instalation, air sucktion from below, supply of treated air ahead. 
IOP - for mounting behind the suspended ceiling, air suction from behind, supply of treated air ahead. 
Recessed duct performances 
COP - for horizontal ceiling mounting in the air duct, air suction from behind, supply of treated air ahead.

Construction features 

Housing performances 

Heat exchanger made of copper pipes with aluminum fins, injection-molded brass manifold, Complete with a patented water distributor with low hydraulic resistance. 

Connections can be moved to the right side of the machine directly on the montage site.

Heat exchangers are equipped with an air release and drain valves.

Radial fan of two-way suction with statically and dynamically balanced rotor, mounted directly on the shaft of the three-speed electric motor.

The electric motor is equipped with an built-in thermal protection and permanently connected phase shift capacitor. 

Reticulated filter from useful for double use polypropylene.

 

Model YardyEV MOP-MOT-MVP-MVT

   

15

20

22

25

35

40

45

55

65

75

Cooling power (full)1

max.

kWt

1,02

1,71

1,92

2,42

2,96

3,61

4,12

5,23

6,34

7,19

mid.

kWt

0,87

1,32

1,49

1,95

2,49

2,74

3,19

4,27

5,28

5,97

min.

kWt

0,62

1,09

1,14

1,56

2,00

2,38

2,89

3,78

4,28

5,51

Thermal power (70 °С)2

max.

kWt

2,40

3,74

4,30

5,66

6,51

8,32

8,88

11,70

14,23

17,37

mid.

kWt

2,02

2,81

3,39

4,39

5,45

6,15

6,58

9,32

11,72

14,92

min.

kWt

1,35

2,34

2,64

3,53

4,31

5,26

6,08

7,86

10,01

13,42

Thermal power (50 °С)3

max.

kWt

1,41

2,20

2,52

3,31

3,82

4,88

5,26

6,83

8,36

10,08

Thermal power of the additional water heat exchanger2

max.

kWt

1,40

2,16

2,22

3,01

3,24

3,92

3,93

6,11

6,31

6,81

mid.

kWt

1,16

1,72

1,97

2,56

2,78

3,41

3,41

5,16

5,80

6,20

min.

kWt

0,98

1,48

1,64

2,07

2,30

3,02

3,04

4,55

5,58

5,64

Air consumption

max.

m3/h

209

288

339

484

547

676

681

1077

1235

1480

mid.

m3/h

163

207

238

339

434

472

474

802

948

1171

min.

m3/h

100

155

177

252

329

390

431

662

757

994

Sound power

max.

dB(A)

43

44

48

48

50

52

52

61

62

66

mid.

dB(A)

35

35

40

38

43

43

43

52

56

61

min.

dB(A)

26

28

32

30

36

38

41

47

50

57

Sound pressure 4

max.

dB(A)

35

36

40

40

42

44

44

51

54

58

mid.

dB(A)

27

27

32

30

35

35

35

44

48

53

min.

dB(A)

18

20

24

22

28

30

33

39

42

49

Maximum power consumption

 

Wt

32

30

38

45

54

72

70

115

161

184

Power supply

W-faz-Hz

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

L - Width

 

mm

700

800

800

1000

1000

1200

1200

1500

1500

1500

H - Height

 

mm

570

570

570

570

570

570

570

570

570

570

H - Height of the legs of the lattice

 

mm

100

100

100

100

100

100

100

100

100

100

P - Depth

 

mm

220

220

220

220

220

220

220

220

220

220

Weight

 

kg

25

31

31

38

39

43

44

55

55

57

×